Engineering and remote access
7.5 SIMATIC STEP 7
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
219
●
Activate web server on this module
Define whether this device can be accessed via the web server. You can find more
information about the web server in Chapter "Web server (Page 270)".
●
Enable automatic update
When you enable "Automatic update" then the actual values of the SITOP PSU8600 and
connected supplementary modules are sent to the web server.
●
Update interval
You define in which intervals the actual values are sent to the web server.
●
Enable automatic logoff
You define whether, after closing the web server, the user is automatically logged off.
●
Permit access only with HTTPS
Define whether access is only permissible with HTTPS.
7.5.4.3
Parameterizing output 1
The procedure is the same for all parameters. This section describes the general procedure
to reach the configuration dialog. The individual parameters and their possible values are
described in the following sections.
Preconditions
●
The SITOP PSU8600 was integrated in the opened project.
●
When configuring an expansion module, this must be assigned to the SITOP PSU8600.
Procedure
1.
Select the SITOP PSU8600 or the expansion module in the "HW Config" view.
2.
Double-click on the required module of the outputs.
3.
Open the "Parameter" tab.
You will see the subgroups of the parameters.
Parameter output 1
Parameter
Value range
Default setting
Switch on output
Yes/no
No
Setpoint output voltage
4 - 28 V
24.0 V
Response threshold of the output current
2 - 20 A or 4 - 40 A
20 A or 40 A
Prewarning threshold output current
0 - 100 %
90 %
On delay
Dependent on the settings in
the basic unit
None
Operating mode
ELECTRONIC
SHUTDOWN / CONSTANT
CURRENT
ELECTRONIC
SHUTDOWN