Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
271
7.7.1
Activating the web server
Activating the web server for the first time (MANUAL operating mode)
NOTICE
Preventing unauthorized access to the web server
Change the password immediately after logging onto the web server for the first time.
Using the web server with the default password represents a security risk.
If the SITOP PSU8600 power supply is in the initial state when originally supplied, then
proceed as follows to activate the web server.
Preconditions
●
The SITOP PSU8600 power supply system is shut down.
●
DIP switch "REN" (Remote enable) is set to "OFF" (MANUAL operating mode is
activated).
●
At the PC interface, 192.168.20.0 is set for the subnet (the same subnet as at the
device).
Procedure
1.
Set DIP switch "WEN" at the basic unit SITOP PSU8600 to "ON".
The web server is activated for the MANUAL operating mode.
2.
Switch on the SITOP PSU8600.
Note
After the system is switched on for the first time with activated web server, the power
supply system generates an SSL certificate to access the web server.
3.
Wait for approximately two minutes until the SSL certificate has been generated and
access to the web server has been activated.
4.
Open the web browser.
Enter the preset IP address of the SITOP PSU8600 in the address field of the web
browser: https://192.168.20.173.
5.
Press the enter key.
The system overview page opens with essential component diagnostic parameters.