Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
298
Manual, 09.2018, A5E36758446-5-76
●
Time B: Duration of short-time interruption
The parameter is used to define the time for which output 1 is interrupted during buffering
when the power returns (for example to restart a PC after it has been run down).
●
Time C: Waiting time after shutdown completed
The parameter is used to define the time that must additionally elapse after the shutdown
has been completed (i.e. after the client can no longer be accessed via a network ping),
before the output voltage at output 1 is interrupted when the power supply returns during
buffering.
●
Define that only output 1 is activated when starting from a battery module
If the SITOP PSU8600 is activated with the energy from a battery module, then only
output 1 is activated. The other outputs are only activated once the supply voltage is
connected/is available.
●
Preferred UPS module when the line supply fails
If there are two UPS modules in the system, then it can be defined as to whether a
certain USP module is the preferred module when starting buffer operation when the line
supply fails - or if this should take place alternating between the two UPS modules.
●
Preferred charging mode for a system start
The power supply system can be configured so that all of the buffer modules and battery
modules are charged up to a specified level before the power supply system outputs are
activated.
You can find additional information on configuring the outputs in Chapter "Operator control at
the device (Page 79)".
Procedure
1.
Select the "Hardware configuration" menu.
2.
Select submenu "Device configuration".
3.
Select the entry of the required "PSU8600".
4.
Make the required settings in the editor area.
5.
Load the data to the device, see Chapter "Loading the configuration (commissioning)
(Page 277)".