Engineering and remote access
7.7 Web server
Power supply system SITOP PSU8600
292
Manual, 09.2018, A5E36758446-5-76
Procedure for setting up a guest access
1. Select the "Hardware configuration" menu.
2. Select submenu "General > User administration".
3. Enter the password in the editor area under "guest" and select the individual access
rights for guest access.
4. Enter the password again under "Confirm password".
5. Load the data to the device.
Procedure for setting up a user account
1. Select the "Hardware configuration" menu.
2. Select submenu "General > User administration".
3. In the editor area, click on "Add new user" and in this line enter the name for the new
user.
4. Select the individual access rights for the new user.
5. Enter a password for the new user - and repeat this to confirm the password.
6. Load the data to the device.
7.7.7.8
Configuring SITOP PSU8600
You change the following settings for the SITOP PSU8600 via the web server:
●
Under "General"
– Prioritized buffering of output 1 enabled
– Soft output characteristic
– System start characteristics
– Threshold for system output current prewarning
– Dead time for system output current prewarning
– General prewarning threshold for individual output current in MANUAL mode
– Dead time for alarm message 'Input voltage outside permitted range'
●
Under "PROFIenergy" you can see the energy management configured via PROFINET.
●
Under "Buffering" you change parameter settings and buffering properties.
●
You configure the output under "Output 1".