Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
229
Input data SITOP BUF8600
SITOP BUF8600 100 ms/40 A and SITOP BUF8600 300 ms/40 A
Slot
Subslot Data
Description
Data size
1-6
1
Internal supply voltage
Internal supply voltage
Unsigned16
Internal buffer voltage
Internal voltage of the energy storage
Unsigned16
Fill byte(s)
reserved
Unsigned16
Fill byte(s)
reserved
Unsigned16
Buffer operation state
Operating state of the buffer module
SITOP BUF8600.
Unsigned8
SITOP BUF8600 4 s/40 A and SITOP BUF8600 10 s/40 A
Slot
Subslot Data
Description
Data size
1-6
1
Internal supply voltage
Internal supply voltage
Unsigned16
Internal buffer voltage
Internal voltage of the energy storage
Unsigned16
Fill byte(s)
reserved
Unsigned16
Fill byte(s)
reserved
Unsigned16
Buffer operation state
Operating state of the buffer module
SITOP BUF8600
Unsigned8
Charging state [0-100%]
Charge state of the buffer module
SITOP BUF8600.
Unsigned8
Buffering disabled by input [0/255]
Buffer module SITOP BUF8600 was
deactivated via the control contact.
Unsigned8
Detailed information about the individual operating states can be found in Section "Operating
states SITOP BUF8600 (Page 236)".
Input data SITOP UPS8600
Slot
Subslot Data
Description
Data size
1-6
1
Actual charging power
Actual charging power
Unsigned16
Maximum permitted charging power
Maximum permitted charging power
Unsigned8
State of charge
Charge status
Unsigned8
Operating state
Operating state
Unsigned8
Fill byte(s)
-
Unsigned16
Battery modules SITOP BAT8600
Slot
Subslot Data
Description
Data size
1-6
2-6
Battery operating state
Operating state of the battery module
Unsigned8
Fill byte(s)
-
Unsigned8
Note
For battery modules from third-party suppliers, only restricted information (sub slot 2) can be
output.