Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
259
Data
Description
Data type
7 = Running
Output switched on (nor-
mal operation)
8 = Overload
Output in overload mode:
9 = Limit
Output current limited to
response threshold:
10 = Overloaded
(SystemOverload)
Output in overload mode
(with derating):
11 = LimitAfter
(SystemOverload)
Output current limited
(with derating)
12 = Locked
Output switched off as the
UPS8600 is being
charged
Output2 Utarget
[10mV], Output2 Ilimit
[10mA] … Output2
operation state
See data, "Output 1"
Output3 Utarget
[10mV], Output3 Ilimit
[10mA] … Output3
operation state
See data, "Output 1"
Output4 Utarget
[10mV], Output4 Ilimit
[10mA] … Output4
operation state
See data, "Output 1"
Output5 Utarget
[10mV], Output5 Ilimit
[10mA] … Output5
operation state
*)
See data, "Output 1"
Output6 Utarget
[10mV], Output6 Ilimit
[10mA] … Output6
operation state
*)
See data, "Output 1"
Output7 Utarget
[10mV], Output7 Ilimit
[10mA] … Output7
operation state
*)
See data, "Output 1"
Output8 Utarget
[10mV], Output8 Ilimit
[10mA] … Output8
operation state
*)
See data, "Output 1"
LED color
Actual LED color. Each
LED is represented by 2
bits:
•
Bit0/1: OK
•
Bit2/3: Output1
•
Bit4/5: Output2
•
Bit6/7: Output3
•
Bit8/9: Output4
•
Bit10-15: unused = 0
0
LED is off.
Unsigned16
Unsigned32
*)
1
LED lit green.
2
LED lit red.
3
LED lit yellow.