Engineering and remote access
7.6 Cyclic and acyclic data
Power supply system SITOP PSU8600
266
Manual, 09.2018, A5E36758446-5-76
Data
Description
Data type
2 = Default
Complete buffer readi-
ness: The energy storage
device of the UPS module
is fully charged (normal
operation).
3 = Defect
Battery module defective
4 = ChargingRestrict-
ed
Battery charging is re-
stricted.
5 = EndOfLife-
timeReached
End of lifecycle has been
reached.
6 = MaintenaceRe-
quired
Maintenance required.
7 = Change completed Battery module success-
fully replaced.
8 = Battery defective
Battery module defective
9 = Not ready for buff-
ering
Battery module is not fully
charged and is not ready
for buffering.
10 = Not completely
loaded but ready for
buffering
Battery module is not fully
charged, but is ready for
buffering.
11 = Ready for buffer-
ing
Ready for buffering.
12 = DeepDischarge-
Recovery
Battery module was deep-
discharged and is in the
recovery phase.
Contact-
ReadyToBuffer
0/255
Unsigned8
Contact-
BufferOperation
0/255
Unsigned8
Contact-OK
0/255
Unsigned8
Contact-
ReadyToBuffer
0/255
Unsigned8
Input-BufferDisable
0/255
Unsigned8
Input-StartFromBattery
0/255
Unsigned8
LED color
Actual LED color. Each
LED is represented by 2
bits:
•
Bit0/1: OK
•
Bit2/3: BAT.
•
Bit4/5: Battery 1:
•
Bit 6/7: Battery 2:
•
Bit 8/9: Battery 3:
•
Bit 10/11: Battery 4:
•
Bit 12/13: Battery 5:
•
Bits 14-15: Not used
0
LED is off.
Unsigned16
1
LED lit green.
2
LED lit red.
3
LED lit yellow.