Description, device design, dimension drawing
2.6 Connections and terminal designations
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
35
2.6.3
Buffer modules
Note
Terminals, only for buffer modules with double-layer capacitors
The subsequently described terminals are only available for buffer modules with double layer
capacitors (BUF8600 4 s / 40 A and 10 s / 40 A).
Using control contact "ON"
④
, the buffer readiness of the buffer module can be activated
and deactivated and/or an active buffer mode exited.
Using signaling contact "Sufficient buffer readiness", "READY"
⑤
signals as to whether the
buffer module has reached an adequate charge state.
Using signaling contact buffer mode "BUF"
⑥
the system signals that it is currently in the
buffer mode.
Connections and terminal designations
④
Control contact "ON" X1, X2
Common plug-in terminal, each with a
screw connection
⑤
Signaling contact Sufficient buffer readiness
"READY" 13, 14
⑥
Signaling contact Buffer mode "BUF" 23, 24
See the diagram in Section "Description of the buffer modules (Page 21)".
Terminal data 6EP4293-8HB00-0XY0, 6EP4295-8HB00-0XY0: