Description, device design, dimension drawing
2.5 Description of the battery modules
Power supply system SITOP PSU8600
Manual, 09.2018, A5E36758446-5-76
31
Figure 2-3
Typical buffer times for a new, completely charged BAT8600 LiFePo4 battery module at
an ambient temperature of 25 °C
NOTICE
Before the first buffer operation in the application itself, it is absolutely crucial that new
battery modules are fully charged continuously without any interruption over a period of 48
hours.
NOTICE
LiFePO4 battery modules, which have been fully discharged in buffer operation, must be
fully charged again within 14 days to avoid the batteries being destroyed as a result of a
deep discharge condition.
The unnecessary deep discharge of the battery module when buffering can be prevented
by limiting the buffer time (see Chapter "Specifying the buffer time limiting (Page 107)").
Additional information about the battery modules is also provided in Chapter "Service life and
storing the batteries (Page 139)".