Description, device design, dimension drawing
2.7 Operator controls
Power supply system SITOP PSU8600
40
Manual, 09.2018, A5E36758446-5-76
⑤
DIP switch "PRY1"
Prioritizes output 1 in the case of a buffering (function is only
available when a CNX8600 expansion module is being used);
see Chapter "Prioritization when the line supply fails (Page 91)".
⑥
DIP switch "UI-1"
Defines the response of the output when an overload occurs;
see Chapter "ELECTRONIC SHUTDOWN and CONSTANT
CURRENT operating modes (Page 93)".
⑦
,
⑧
DIP switch "STDA",
"STDB"
Defines the switch-on sequence of the outputs (function is only
available when a CNX8600 expansion module is being used);
see Chapter "Setting the on delay (Page 95)".
⑨
DIP switch "SOC1"
Switchover between the regular and soft output characteristic,
see Chapter "Setting the output characteristic (Page 97)".
⑩
DIP switch "FUNC"
no function
⑪
DIP switch "WEN"
Activates and deactivates the integrated web server, see Chap-
ter "Activate the web server for the MANUAL operating mode on
the module (Page 98)".
Protection and sealing
The operating elements (with the exception of the buttons), are protected against accidental
operation by a transparent plastic cover. When required, this plastic cover can be sealed to
prevent the operating elements being actuated by unauthorized personnel. To seal, the
sealing wire is routed through an opening in the plastic cover and housing, as shown in the
following diagram.