Description, device design, dimension drawing
2.6 Connections and terminal designations
Power supply system SITOP PSU8600
32
Manual, 09.2018, A5E36758446-5-76
2.6
Connections and terminal designations
2.6.1
Basic devices
The line input terminals
①
can be used to establish the connection to supply voltage. The
output terminals
②
and the 0 V terminal
③
are the load connections. A ground connection
to other supplementary modules can be established using the 0 Volt terminal
③
.
The operating state of the device can be interrogated using signaling contact
④
. The reset
terminal
④
is used for a remote reset of the electronic overload shutdown.
Ethernet/PROFINET cables (RJ45 plug connection 8P8C) are connected at the
Ethernet/PROFINET interface
⑤
for PROFINET operation.
Connections and terminal designations
①
Line input L1, L2, L3, PE
Plug-in terminal each with a screw connection
②
Output 1
Plug-in terminal with two screw connections
③
0 Volt terminal 0 V
Plug-in terminal with three screw connections
④
Signaling contact 11, 12, 14
Remote reset RST
Common plug-in terminal with a screw connection
⑤
PROFINET (2-port switch)
RJ45 8P8C plug connection
See the diagram in Section "Description of the basic devices (Page 17)".
Terminal data 6EP3436-8SB00-2AY0:
*1) Do not subject the end stop to high loads
*2) Derating 18 A/60 °C or 20 A/50 °C