Operation
11/03
SINAMICS G150
6-28
Operating Manual
Setting range: -20.000 ... +20.000 V or mA
p4059[0]
Value x2 for the analog input
characteristic
Factory setting: 20.000 mA
Setting for the x coordinate in V or mA of the second point on the scaling characteristic.
The unit is V when analog input 0 is set as a voltage input (p4056 = 0 / 4) and switch S5.0 is set to "V".
The unit is mA when analog input 0 is set as a current input (p4056 = 2 / 3 / 5) and switch S5.0 is
set to "I".
Setting range: -1000.00 ... +1000.00 %
p4060[0]
Value y2 for the analog input
characteristic
Factory setting: 100.00 %
Setting for the y coordinate in % of the second point on the scaling characteristic.