Diagnosis / Faults and Alarms
11/03
SINAMICS G150
10-46
Operating Manual
F30883
CU DRIVE-CLiQ: Hardware defect
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy:
- Replace Control Unit.
Acknowl.: Immediate
F30884
CU DRIVE-CLiQ: Redundancy link error
Reaction: OFF2
Cause:
Reserved for later use.
Remedy:
Reserved for later use.
Acknowl.: Immediate
F30885
CU DRIVE-CLiQ: fault in cyclic data transfer
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.: Immediate
F30886
CU DRIVE-CLiQ: Data transfer faulted
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy:
- Check firmware states of affected components.
- Replace affected component.
Acknowl.: Immediate
F30887
F30888
CU DRIVE-CLiQ: Hardware defect
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy:
Replace Control Unit.
Acknowl.: Immediate
F30889
CU DRIVE-CLiQ: Data transfer faulted
Reaction: OFF2
Cause:
DRIVE-CLiQ communication between control unit and at least one other component is
defective.
Fault value
(r0949):
Bit 0 - 7: Number of the affected component
Bit 8 - 31: Reserved
Remedy:
- Check for break in DRIVE-CLiQ or faulty contacts in connector.
- Check 24 V supply of affected component.
- Replace affected component.
Acknowl.: Immediate
F30890
CU DRIVE-CLiQ: Connection setup
Reaction: OFF2
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......