11/03 Electrical
Installation
SINAMICS G150
Operating Manual
4-37
Duty Cycles
10
20
30
40
50
60
70
80
90 100 110 120 130
0.25
0.50
0.75
1.00
1.25
1.50
P/P
20
t/s
P
15
P
20
P
40
P
DB
P
DB
= Continuous braking power
P
15
= 5 x P
DB
= Power permissible every 90s for 15s
P
20
= 4 x P
DB
= Power permissible every 90s for 20s
P
40
= 2 x P
DB
= Power permissible every 90s for 40s
Fig. 4-10
Duty cycles for the braking resistors
Threshold Switch
The response threshold at which the braking unit is activated and the DC link
voltage generated during braking are specified in the following table.
WARNING
The threshold switch must only be used when the cabinet unit is switched off and
the DC link capacitors are discharged.
Table 4-29
Response thresholds for the braking units
Rated voltage Response
threshold
Switch
position
Comments
774 V
1
380 V -480 V
673 V
2
774 V is the default factory setting. With supply voltages of
between 380 V and 400 V, the response threshold can be set
to 673 V to reduce the voltage stress on the motor and
converter. This does, however, reduce the possible peak
power (P
15
) with the square of the voltage (677/774)² = 0.75.
The possible peak power is, therefore, max. 75 % of P
15
.
660 V -690 V
1158 V
1
1158 V is the default factory setting. With a supply voltage of
660 V, the response threshold can be set to 1070 V to reduce
the voltage stress on the motor and converter. This does,
however, reduce the possible peak power (P
15
) with the
square of the voltage (1070/1158)² = 0.85.
The possible peak power is, therefore, max. 85 % of P
15
.
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......