Monitoring, Functions, and Protective Functions
11/03
SINAMICS G150
9-8
Operating Manual
Setting Parameters
Setting range: 0 ... 6
p1200
Flying restart operating mode
Factory setting: 1
Setting the flying restart mode.
Values: 0: Flying restart is disabled
1: Flying restart is always active, start in direction of setpoint
2: Flying restart is active, with line ON, error, OFF2, start in direction of setpoint
3: Flying restart is active, with error, OFF2, start in direction of setpoint
4: Flying restart is always active, in direction of setpoint only
5: Flying restart is active, with line ON, error, OFF2, in direction of setpoint only
6: Flying restart is active, with error, OFF2, in direction of setpoint only
In operating modes 1 to 3, the search is carried out in both directions; in operating modes 4 to 6, the
search is carried out in the setpoint direction only.
Setting range: 10 ... 400 %
p1202
Flying restart detection current
Factory setting: 100 %
Defines the detection current for the flying restart function. The value refers to the rated motor current.
Setting range: 10 ... 400 %
p1203
Flying restart search rate
Factory setting: 100 %
This factor influences the rate at which the output frequency changes during the flying restart.
The higher the value, the longer the search time.
Settings
9.4 Protective
Functions
(in preparation)
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......