Output Terminals
11/03
SINAMICS G150
8-10
Operating Manual
Example: Changing Analog Output 0 from Current to Voltage Output –10 - +10 V
and Setting the Characteristic
Set TM31.AO_type [analog output 0] to -10 - +10 V
p4077[0] = 0.00
p4080[0] = 10.000
Set TM31.AO_charac. y1 to 0.000 V
p4076[0] = 4
Set TM31.AO_charac. x1 to 0.00%
X522: 1,2
Voltage output present at terminal 1, ground at terminal 2
p4078[0] = 0.000
p4079[0] = 100.00
Set TM31.AO_charac. x2 to 100.00%
Set TM31.AO_charac. y2 to 10.000 V
Fig: 8-5
Example: Setting analog output 0 and the characteristic