Electrical Installation
11/03
SINAMICS G150
4-24
Operating Manual
X541: 4 Non-Floating Digital Inputs/Outputs
Table 4-14
Terminal block X541
Terminal
Designation
1)
Technical data
Factory Setting
1 P24
2
DI/DO 8
DO8: ready to start
3
DI/DO 9
DO9: LOCAL mode active
4
DI/DO 10
DO10: Enable pulses
5 DI/DO
11
1
2
3
4
5
6
6 M
As input:
Voltage: -3 V to 30 V
Current input (typical):
10 mA at 24 V DC
As output:
Max. load current per output:
20 mA
Sustained short circuit proof
1)
DI/DO: digital input/output; M: electronic ground
Max. connectable cross-section: 1.5 mm² (AWG 14)
NOTE
An open-circuit input is interpreted as "low".
X542: 2 Relay Outputs (Two-Way Contacts)
Table 4-15
Terminal block X542
Terminal
Designation
1)
Technical data
Factory Setting
1 DO
0.NC
2 DO
0.NC
3 DO
0.NO
Checkback
Enable pulses
4 DO
1.NC
5 DO
1.COM
1
2
3
4
5
6
6 DO
1.NO
Max. load current: 8 A
Max. switching voltage:
250 V AC, 30 V DC
Max. switching capacity:
at 250 V AC: 2000 VA
at 30 V DC: 240 W (ohmic load)
Required minimum load: 20 mA
Checkback
No fault
1)
NO: normally open contact, NC: normally closed contact, COM: mid-position
contact
Max. connectable cross-section: 2.5 mm² (AWG 12)
NOTE
If 230 V AC is applied to the relay outputs, the customer terminal block must also
be grounded via a 6 mm² protective conductor.
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......