Technical Data
SINAMICS G150
Operating Manual
12-3
12.2.1 Derating
Data
Current Derating as a Function of the Site Altitude and Ambient Temperature
If the cabinet units are operated at a site altitude >2000 m above sea level, the
maximum permissible output current can be calculated using the following tables.
The site altitude and ambient temperature are compensated here. The degree of
protection selected for the cabinet units must also be taken into account.
Table 12-2
Current derating as a function of the ambient temperature and site altitude for cabinet units
with degree of protection IP20 / IP21 and IP23
Ambient temperature in °C
Site altitude
above sea level in
m
20
25
30
35
40
45
50
0 to 2000
95.0% 90.0%
Up to 2500
100%
96.3% 91.4% 86.6%
Up to 3000
96.2% 92.5% 87.9% 83.3%
Up to 3500
96.7% 92.3% 88.8% 84.3% 79.9%
Up to 4000
97.8% 92.7% 88.4% 85.0% 80.8% 76.5%
Table 12-3
Current derating as a function of the ambient temperature and site altitude for cabinet units
with degree of protection IP54
Ambient temperature in °C
Site altitude
above sea level in
m
20
25
30
35
40
45
50
0 to 2000
98.0% 93.0% 90.0% 85.0% 81.0%
Up to 2500
100%
99.0% 94.0% 90.0% 86.0% 82.0% 77.0%
Up to 3000
95.0% 90.0% 86.0% 83.0% 79.0% 74.0%
Up to 3500
96.0% 91.0% 87.0% 83.0% 80.0% 75.0% 71.0%
Up to 4000
92.0% 87.0% 83.0% 79.0% 76.0% 72.0% 68.0%
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......