11/03 Electrical
Installation
SINAMICS G150
Operating Manual
4-23
S5: Selector for Voltage/Current AI0, AI1
Table 4-11
Selector for voltage/current S5
Switch Function
Technical
data
S5.0
Selector voltage/current AI0
S5.1
Selector voltage/current AI1
Voltage
S5.0
S5.1
V
I
I
V
Current
X522: 2 Analog Outputs, Temperature Sensor Connection
Table 4-12
Terminal block X522
Terminal
Designation
1)
Technical data
Factory Setting
1
AO 0 V+
2
AO 0 ref.
3
AO 0 A+
Actual speed value:
0 – 20 mA
4
AO 1 V+
5
AO 1 ref.
6
AO 1 A+
-10 V - +10 V
+4 mA - +20 mA
-20 mA - +20 mA
0 mA - +20 mA
Motor current actual
value:
0 – 20 mA
7 KTY+
8
7
6
5
4
3
2
1
8 KTY-
KTY84: 0...200 °C
PTC: R
PTC
≤
1.5 k
Ω
1)
AO: analog output; KTY: temperature sensor connection
Max. connectable cross-section: 1.5 mm² (AWG 14)
X540: Common Auxiliary Voltage for Digital Inputs
Table 4-13
Terminal block X540
Terminal
Designation
Technical data
Factory Setting
1 P24
2 P24
3 P24
4 P24
5 P24
6 P24
7 P24
8
7
6
5
4
3
2
1
8 P24
24 V DC
Imax = 150 mA (total of all P24
terminals)
Max. connectable cross-section: 1.5 mm² (AWG 14)
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......