![Siemens SINAMICS G150 Operating Manual Download Page 122](http://html.mh-extra.com/html/siemens/sinamics-g150/sinamics-g150_operating-manual_378200122.webp)
Setpoint Channel and Closed-Loop Control
11/03
SINAMICS G150
7-6
Operating Manual
Setting Parameters
Setting range: 0.00 ... 999999.00 s
p1120
Ramp generator ramp-up time
Factory setting: 10.00 s
During this interval, the setpoint increases from zero to the speed limit (p1082).
Setting range: 0.00 ... 999999.00 s
p1121
Ramp generator ramp-down time
Factory setting: 10.00 s
During this interval, the setpoint decreases from the speed limit (p1082) to zero.
Setting range: 0.00 ... 30.00 s
p1130
Ramp generator start rounding time
Factory setting: 0.00 s
Setting for the start rounding time. The value applies to ramp-up and ramp-down.
Setting range: 0.00 ... 30.00 s
p1131
Ramp generator end rounding time
Factory setting: 0.00 s
Setting for the end rounding time. The value applies to ramp-up and ramp-down.
NOTE
The effective ramp-up time increases when you enter a start and end rounding
time.
Effective ramp-up time = p1120 + (0.5 x p1130) + (0.5 x p1131)
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......