![Siemens SINAMICS G150 Operating Manual Download Page 165](http://html.mh-extra.com/html/siemens/sinamics-g150/sinamics-g150_operating-manual_378200165.webp)
11/03
Diagnosis / Faults and Alarms
SINAMICS G150
Operating Manual
10-23
Acknowl.: Immediate
F1800
DRIVE-CLiQ: Hardware/configuration defective
Reaction: OFF2
Cause:
An error occurred on the DRIVE-CLiQ interface.
Fault value
(r0949):
0..3: Port 0..3 has not switched to cyclic mode.
The cause may be an incorrect setup or configuration that produces inconsistent
bus timings.
10 : Loss of Drive-CLiQ connection
Cause, e.g. Drive-CLiQ cable has been removed from CU.
This error cannot be acknowledged until communication is cyclic again.
11 : Repeated error for connection ID.
This error cannot be acknowledged until communication is cyclic again.
12 : A connection was detected but exchange of the station ID does not work.
probable cause: defective component.
This error cannot be acknowledged until communication is cyclic again.
Remedy:
For fault values 0 ... 3:
- Ensure that the software statuses of the DRIVE-CliQ components are the same.
- Avoid long topologies with short current controller cycles.
For fault value 10:
- Check the DRIVE-CliQ cables on the control unit.
- POWER ON.
For fault value 11:
- Ensure that the cabinet and cabling are EMC compliant.
For fault value 12:
- Replace the affected component.
Acknowl.: Immediate
F1801
DRIVE-CLiQ: No communication to component
Reaction: OFF2
Cause:
A communication with the DRIVE-CLiQ component indicated by the fault value is not
possible.
Cause may be that a Drive-CLiQ cable has been pulled out.
Remedy:
- Check the DRIVE-CliQ cables.
- POWER ON.
Acknowl.: Immediate
F1802
CU DRIVE-CLiQ: Modification of DRIVE-CLiQ basic clock cycle times requires POWER ON
Reaction: OFF2
Cause:
Modification of DRIVE-CLiQ basic clock cycle times p0110 is not possible during operation.
Fault value
(r0949):
Index of p0110.
Remedy:
Save (p0971 = 1), switch OFF and ON again.
Acknowl.: POWER
ON
A1900
PROFIBUS: Configuration telegram faulted
Cause:
PROFIBUS master is attempting to set up a connection using a wrong configuration
telegram.
Alarm value
(r2124):
50: Syntax error
51: Connection setup to more drives than configured in the unit
52: More than 16 input or output data words for a drive
53: Uneven number of input or output bytes
Remedy:
Check the bus configuration:
- Slave configuration
A1901
PROFIBUS: Parameteriz. telegram faulted
Cause:
A PROFIBUS master is attempting to set up a connection using an incorrect configuration
telegram.
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......