11/03
Operation
SINAMICS G150
Operating Manual
6-13
6.2.3.4 Switching
Between
Clockwise and Counter-Clockwise Rotation
Settings: MENU – Settings – Control Settings
Switching between CW/CCW
(factory setting: no)
•
Yes
: Switching between CW/CCW rotation by means of the CW/CCW key
possible in LOCAL mode
•
No
: The CW/CCW key has no effect in LOCAL mode
For safety reasons, the CW/CCW key is disabled in the factory setting (pumps and
fans must normally only be operated in one direction).
In the operation status in LOCAL mode, the current direction of rotation is indicated
by an arrow next to the operating mode.
6.2.3.5
Jog (reserved for future use)
6.2.3.6 Increase
Setpoint / Decrease Setpoint
You can use the “increase” and “decrease” keys to set the setpoint with a
resolution of 1 % of the maximum speed.
(e.g. if the resolution is 15 min
-1
at p1082 = 1500 min
-1
)
You can also enter the setpoint numerically. To do so, press F2 in the operation
screen. The system displays an inverted edit field for entering the required speed.
Enter the required value using the numeric keypad. Press F5 OK to confirm the
setpoint.
When you enter values numerically, you can enter any speed between the
minimum speed (p1080) and the maximum speed (p1082).
Setpoint entry in LOCAL mode is unipolar. You can change the direction of rotation
by pressing the +/- keys (see Section 6.2.3.4).
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......