Electrical Installation
11/03
SINAMICS G150
4-32
Operating Manual
4.9.9
EMERGENCY OFF Category 1; 24 V DC (Option L60)
Description
EMERGENCY OFF category 1 for controlled stop to EN 60 204. This function
involves stopping the drive by means of a rapid stop using a deceleration ramp that
can be parameterized by the user. The cabinet unit is then disconnected from the
supply via the line contactor bypassing the electronics by means of a safety
combination to EN 60 204-1. A braking unit may be necessary to achieve the
required shutdown times.
The operational status is indicated by means of five LEDs.
Connection
Table 4-24
Terminal block X120 – connection for EMERGENCY OFF category 1 (24 V
DC)
Terminal
Button circuit 24 V DC
7
8
Loop in EMERGENCY OFF button from system side,
remove jumper 7-8
15
16
"On" for monitored start:
remove jumper 15–16 and connect button
17
18
Checkback "trip safety combination"
Max. connectable cross-section: 4 mm² (AWG 10)
Setting
When the emergency stop function (OFF3 ramp-down time, p1135) is used to shut
down the drive, the ramp-down time should be less than (or at the most equal to)
the time set on the contactor combination, after which the converter is de-
energized.
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs) are
described in “Additional Operating Instructions” in the operating manual.
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......