Technical Data
11/03
SINAMICS G150
12-8
Operating Manual
12.3.2
Cabinet Unit Version C, 380 V – 480 V
Table 12-9
Version C, 380 V – 480 V, part 1
Category Unit
Order no.
6SL3710-
1GE32-1CA0 1GE32-6CA0 1GE33-1CA0
Rated motor output
kW
110
132
160
Rated connection voltage
V
3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
Rated input current
A
239
294
348
Rated output current
A
210
260
310
Base load current
A
205
250
302
Power loss
kW
2.9
3.8
4.4
Cooling air requirement
m³/s
0.17
0.23
0.36
Sound pressure level at 50/60
Hz
dB(A) 67/68
69/73
69/73
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 70
2 x (000)
2 x 240
2 x (600)
M12 (1 hole)
2 x 95
2 x (4/0)
2 x 240
2 x (600)
M12 (1 hole)
2 x 120
2 x (300)
2 x 240
2 x (600)
M12 (1 hole)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 70
2 x (000)
2 x 150
2 x (400)
M12 (1 hole)
2 x 95
2 x (4/0)
2 x 150
2 x (400)
M12 (1 hole)
2 x 120
2 x (300)
2 x 150
2 x (400)
M12 (1 hole)
Protective earth connection
Fastening screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard
version)
kg 225
225
300
Dimensions (w x h x d)
mm
400 x 2000 x 600
400 x 2000 x 600
400 x 2000 x 600
Recommended protection
Cond./semi-cond. protection
Rated current
Size to DIN 43 620-1
A
3NE1 230-2
315
1
3NE1 231-2
350
2
3NE1 334-2
500
2
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......