11/03 Electrical
Installation
SINAMICS G150
Operating Manual
4-13
Fig. 4-1
Setting terminals for the fan transformer (380 V – 480 V / 660 V – 690 V)
The supply voltage assignments for making the appropriate setting on the fan
transformer are indicated in the following table.
NOTE
With the 660 V – 690 V fan transformer, a jumper is inserted between terminal
“600 V” and terminal “CON”. Terminal “CON” is for internal use.
IMPORTANT
If the terminals are not reconnected to the actual supply voltage:
•
the required cooling capacity cannot be provided because the fan rotates too
slowly
•
the fan fuses may blow due to an overcurrent.
NOTE
The order numbers for fan fuses that have blown can be found in the spare parts
list.
Table 4-3
Supply voltage assignments for the fan transformer setting (380 V - 480 V)
Supply voltage
Fan transformer tap (-U1 -T10)
342 V - 390 V
380 V
391 V - 430 V
400 V
431 V - 460 V
440 V
461 V - 528 V
480 V
Table 4-4
Supply voltage assignments for the fan transformer setting (660 V - 690 V)
Supply voltage
Fan transformer tap (-U1 -T10)
600 V - 630 V
600 V
631 V - 680 V
660 V
681 V - 759 V
690 V