Output Terminals
11/03
SINAMICS G150
8-8
Operating Manual
8.4
Further Settings for Analog Outputs
Description
The customer terminal block (–A60) features two analog outputs for outputting
setpoints via current or voltage signals.
In addition to the settings described in Chapter 8.2, a function for scaling output
signals is available.
Signal Flow Diagram
D
A
AO_type
p4076
AO 0V+
AO 0A+
AO 0 Bez
X522.1
X522.2
X522.3
Output
voltage
Current output
+-10V
+-20mA
Smoothing
Smoothing
p4073
AO Signal
p4071
act. V/I
r4074
Actual speed
r0063
DC-link voltage
r0070
Output power
r0082
Output current
r0068
...
Scaling
Char. x1
p4077
Char. y2
p4080
x
y
x
1
y
2
x
2
y
1
y
x
[%]
Char. y1
p4078
Char. x2
p4079
Fig. 8-4
Signal flow diagram: Analog output 0
Additional Setting Parameters for Analog Output 0 (AO0)
Setting range: -1000.00 ... +1000.00 %
p4077[0]
Value x1 for the analog output
characteristic
Factory setting: 0.00 %
Setting for the x coordinate in % of the first point on the scaling characteristic.
Setting range: -20.000 ... +20.000 V or mA
p4078[0]
Value y1 for the analog output
characteristic
Factory setting: 0.000 mA
Setting for the y coordinate in V or mA of the first point on the scaling characteristic.
The unit is V when analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 1
and 2 are used.
The unit is mA when analog output 0 is set as a current output (p4076[0] = 0 / 2 / 3) and terminals X522:
3 and 2 are used.
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......