Electrical Installation
11/03
SINAMICS G150
4-30
Operating Manual
4.9.7
EMERGENCY OFF Category 0; 230 V AC or 24 V DC (Option L57)
Description
EMERGENCY OFF category 0 for uncontrolled stop to EN 60 204. This function
involves disconnecting the cabinet from the supply via the line contactor bypassing
the electronics by means of a safety combination to EN 60 204-1. The motor then
coasts to a stop. To prevent the main contactor from switching under load, a pulse
block is triggered at the same time via an external fault. A restart is only possible
after the fault has been acknowledged. The operational status is indicated by
means of three LEDs.
In the factory setting, this version is set with a 230 V AC button circuit.
Connection
Table 4-22
Terminal X120 – connection for EMERGENCY OFF category 0, 230 V AC and
24 V DC
Terminal
230 V AC and 24 V DC button circuit
7
8
Loop in EMERGENCY OFF button from system side,
remove jumper 7-8
15
16
"On" for monitored start:
remove jumper 15–16 and connect button
17
18
Checkback "trip safety combination"
Max. connectable cross-section: 4 mm² (AWG 10)
Reconnection to the 24 V DC Button Circuit
When using the 24 V DC button circuit, you must remove the following jumpers at
terminal X120:
4-5, 9-10, and 11-14
You must also insert the following jumpers at terminal X120:
4-11, 5-10, and 9-14
Diagnostics
Messages output during operation and in the event of faults (meaning of LEDs) are
described in “Additional Operating Instructions” in the operating manual.
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......