11/03
Operation
SINAMICS G150
Operating Manual
6-9
Scaling
Table 6-2
Scaling
Variable
Scaling parameter
Default for quick commissioning
Reference speed
100 % = p2000
p2000 = Maximum speed (p1082)
Reference voltage
100 % = p2001
p2001 = 1000 V
Reference current
100 % = p2002
p2002 = Current limit (p0640)
Reference torque
100 % = p2003
p2003 = 2 x rated motor torque
Reference power
100 % = r2004
30
π
p2000
p2003
r2004
×
×
=
Reference frequency
60
p2000
%
100
=
Reference control factor 100 % = Maximum output voltage
without overload
Reference flux
100 % = Rated motor flux
Reference temperature
100% = 100 °C
Setting the Date / Time
In this menu, you set the date and time.
Setting the Language
In this menu, you can select the active language.
You have a choice between the two languages currently stored in the operator
panel.
If the language you require is not available, you can load it separately (see
Chapter 11).
Menu for Resetting System Settings
You can choose this menu option to reset the following settings to the factory
settings:
•
Language
•
Display (brightness, contrast)
•
Operation screen
•
Control settings
The settings do not become effective until the power supply is next switched on.
IMPORTANT
When you reset parameters, all settings that are different to the factory settings are
reset immediately. This may cause the cabinet unit to switch to a different,
unwanted operational status.
For this reason, you should always take great care when resetting parameters.
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......