11/03
Technical Data
SINAMICS G150
Operating Manual
12-7
Table 12-8
Version A, 380 V – 480 V, part 3
Category Unit
Order no.
6SL3710-
1GE37-5AA0 1GE38-4AA0 1GE41-0AA0
Rated motor output
kW
400
450
560
Rated connection voltage
V
3 AC 380 V to 480 V ±10 % (-15 % < 1 min)
Rated input current
A
785
883
1034
Rated output current
A
745
840
985
Base load current
A
725
820
960
Power loss
kW
9.6
10.1
14.4
Cooling air requirement
m³/s
0.78
0.78
1.48
Sound pressure level at 50/60
Hz
dB(A) 70/73
70/73
72/75
Power connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 300
2 x (800)
4 x 240
4 x (600)
M12 (2 holes)
4 x 150
4 x (400)
8 x 240
8 x (600)
M12 (4 holes)
4 x 185
4 x (500)
8 x 240
8 x (600)
M12 (4 holes)
Motor connection
Recommended: DIN VDE
AWG / MCM
Maximum: DIN VDE
AWG / MCM
Fastening screw
mm
2
mm
2
2 x 300
2 x (800)
4 x 240
4 x (600)
M12 (2 holes)
4 x 150
4 x (400)
4 x 240
4 x (600)
M12 (2 holes)
4 x 185
4 x (500)
6 x 240
6 x (600)
M12 (3 holes)
Protective earth connection
Fastening screw
M12
(10 holes)
M12
(16 holes)
M12
(18 holes)
Approx. weight (standard
version)
kg 865
1075
1360
Dimensions (w x h x d)
mm
1200 x 2000 x 600 1200 x 2000 x 600 1600 x 2000 x 600
Recommended protection
Conductor protection
(with option L26)
Rated current
Size to DIN 43 620-1
Cond./semi-cond. protection
(without option L26)
Rated current
Size to DIN 43 620-1
A
A
3NA3 475
800
4
3NE1 448-2
850
3
Protective device
Circuit-breaker
Protective device
Circuit-breaker
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......