Commissioning
11/03
SINAMICS G150
5-4
Operating Manual
5.3.2 Basic
Commissioning
Entering the Motor Data
During initial commissioning, you have to enter motor data using the operator
panel. Use the data shown on the motor type plate.
p0305
p0311
p0307
p0310
p0304
S
3 ~MOT. 1LA8 315-4PM80 315 No N- 1107840010001/2002 IMB3
V
400
690
Hz
50
A
405
235
kW
235
cos
ϕ
0,87
1/min
1485
I
A
/I
N
T
E
s Certif.
No
IP
55
Rotor SQU.CAGE KL 13 EN/IEC 60034-1 Gew/Wt 1,3 t
NMAX=3000 1/MIN
MADE IN GERMANY
D
E
W
0233
p0308
Fig. 5-3
Example of a motor type plate
Table 5-4
Motor data
Parameter
no.
Values
Unit
System of units for line frequency and entering
motor data
p0100 0
1
IEC [50 Hz / kW]
NEMA [60 Hz / hp]
Motor:
Rated voltage
Rated current
Rated output
Rated power factor Cos
ϕ
(at p0100 = 0 only)
Rated efficiency
η
(at p0100 = 1 only)
Rated frequency
Rated speed
p0304
p0305
p0307
p0308
p0309
p0310
p0311
[V]
[A]
[kW] / [hp]
[%]
[Hz]
[min-1] / [rpm]
Summary of Contents for SINAMICS G150
Page 2: ......
Page 22: ...Device Overview 11 03 SINAMICS G150 2 10 Operating Manual ...
Page 196: ...Diagnosis Faults and Alarms 11 03 SINAMICS G150 10 54 Operating Manual ...
Page 208: ...Maintenance and Servicing 11 03 SINAMICS G150 11 12 Operating Manual ...
Page 234: ......
Page 238: ...Parameterlist 11 03 SINAMICS G150 Parameterlist 4 Operating Manual ...
Page 239: ......