Installation/mounting
5.3 Distributed configuration
SIMOTION P350-3 and Panels
94
Manual, 05/2009
5.3.2
Components for decentralized structure
The decentralized structure comprises several subcomponents based on the modular
principal; it is suitable for all SIMOTION panel fronts:
●
SIMOTION P350-3 (DVI interface and USB 2.0 port)
●
Panel PC Remote Kit for mounting on a TFT operator panel front
●
Cable set for connecting the computing unit and the Panel PC Remote Kit (5 m to 30 m)
●
USB transmit module for cable lengths > 5 m
●
Installation-specific mounting kits, such as
–
Flat mounting brackets for fastening the SIMOTION P350-3 in the control cabinet
–
Book mounting brackets for fastening the SIMOTION P350-3 in the control cabinet
5.3.3
Mounting the Panel PC Remote Kit on a SIMOTION panel front
Procedure
To mount the Panel PC Remote Kit on a SIMOTION panel front, proceed as follows:
1.
Attach the fastening hooks on the remote module to the panel front on the same side as
the connecting cables.
)DVWHQLQJKRRNVIRU
UHPRWHPRGXOH
Figure 5-2
Hooking the remote module into the SIMOTION panel front