Accessories
9.1 Power supply
SIMOTION P350-3 and Panels
122
Manual, 05/2009
9.1.2
Example: SITOP smart 24 V/10 A
The SITOP smart 24 V/10 A power supply meets all requirements of a SIMOTION P350-3
and is, therefore, ideal for this application. This device in particular is the only one that can
cover the inrush current of 14 A for SIMOTION P350-3 that occurs for a short period of time.
Figure 9-1
View of the SITOP smart 24 V/10 A
9.1.3
Technical data for the SITOP smart 24 V/10 A
Table 9- 1
Input data
•
Input voltage rated value
120/230 V AC
•
Input voltage range
85 to 132 V AC/170 to 264 V
•
Power failure bridging
> 20 ms at V
in
= 93/187 V
•
Mains frequency rated value
50/60 Hz
•
Mains frequency range
47 … 63 Hz
•
Input current rated value
4.1/2.4 A
•
Inrush current (at + 25 °C)
< 65 A
•
Recommended miniature circuit breaker
10 A, Characteristic C
Output data
•
Output voltage rated value
24 V DC
•
Output voltage tolerance
± 3 %
•
Residual ripple/spikes
< 150/240 mV
pp
•
Output voltage adjustment range
22.8 to 28 V DC
•
Output current rated value
10 A
(12 A up to + 45 °C)