Connection
6.4 Connecting the (24 V) DC power supply
SIMOTION P350-3 and Panels
102
Manual, 05/2009
6.4
Connecting the (24 V) DC power supply
Note before connecting
WARNING
Only connect the device to 24 V DC power supply systems that meet the requirements of a
protective extra-low voltage (PELV); in addition, a protective conductor must be connected.
The cable cross-section must be dimensioned as appropriate for the short-circuit current of
the 24 V DC power source, so that a short-circuit will not damage the cables. Only connect
cables with a minimum cross-section of 1.3 mm
2
(AWG16) and a maximum cross-section of
3.3 mm
2
(AWG12).
NOTICE
The 24 V DC power source must be adapted to the input data of the device (see Technical
data).
Connecting
Steps for connecting the device to the 24 V power supply
1. Make sure that the On/Off switch is set to "0"
(OFF). Otherwise, the device will start up
unintentionally when the 24 V supply is
connected.
2. Switch off the 24 V DC power source.
3. Connect the DC connector.
See also