Hardware description
3.3 SIMOTION P State application
SIMOTION P350-3 and Panels
46
Manual, 05/2009
3.3.2
LED display
The meaning of the LEDs and their colors is described in the table below.
Table 3- 3
Meaning of LEDs
LED
Meaning
SF (red)
This LED indicates that a fault has occurred on
SIMOTION P.
5 V DC (green)
SIMOTION P voltage on
This LED indicates that the voltage is present at P.
RUN (green) -
SIMOTION P in RUN mode
This LED indicates that the user program is running.
STOPU (yellow) -
SIMOTION P in STOP user program
mode
This LED indicates that the technology packages (for
example, synchronous operation and cam) are active.
Test and commissioning functions can be executed
without a user program. The user program is not active.
STOP (yellow) -
SIMOTION P in STOP mode
This LED indicates that no user program is running. The
technology packages are not active.
BUS1F (red) -
Group fault
This LED indicates a fault on the PROFIBUS DP
interface (X101).
BUS2F (red) -
Group fault
This LED indicates a fault on the MPI/DP interface
(X102).
3.3.3
Mode selector
The mode selector is used to set the SIMOTION P application to different states. You can
switch the control to RUN or STOP/STOPU and perform an overall reset.
A system status activated with the mode selector has priority over a status selected via
SIMOTION SCOUT. Consequently, you cannot switch the control to RUN mode via
SIMOTION SCOUT while the mode selector is set to STOP/STOPU on the
SIMOTION P350-3. You must use the mode selector for this.
Further information for the function of the mode selector switch is available in the following
documentation:
Literature:
SIMOTION P350-3 and Panel Fronts Commissioning and Hardware Installation Manual