Distributed I/O system
54
System Manual, 12/2016, A5E03576849-AG
Installation
4
4.1
Basics
Introduction
All modules of the ET 200SP distributed I/O system are open equipment. This means you
may only set up the distributed I/O system ET 200SP in enclosures, cabinets or electrical
equipment rooms and in a dry environment (IP20 degree of protection). These enclosures,
cabinets or electrical equipment rooms must only be accessible with a key or tool. Access
must only be possible for personnel instructed or authorized to work with such equipment.
Installation location
Install the ET 200SP distributed I/O system into a suitable housing/control cabinet with
sufficient mechanical strength, fire protection and at least IP54 degree of protection
according to EN 60529, and take into consideration the ambient conditions for operating the
devices.
Installation position
You can mount the ET 200SP distributed I/O system in any position. The preferred mounting
position is horizontal mounting on a vertical wall. The ambient temperature may be restricted
in certain installation positions. You will find more information in the section Mechanical and
climatic environmental conditions (Page 279).
You can only install motor starters vertically, horizontally or on their backs. Pay attention to
chapter "Installation conditions for motor starters (Page 58)" when using motor starters.