Commissioning
10.3 Commissioning the ET 200SP on PROFIBUS DP
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
207
Commissioning procedure
For commissioning of the ET 200SP distributed I/O system as an I-slave on the
PROFIBUS DP, we recommend the following procedure:
Table 10- 5 Procedure for commissioning the ET 200SP as an I-slave for PROFIBUS DP
Step
Procedure
See ...
1
Installing ET 200SP (with CPU and CM DP)
Section Installation (Page 54)
2
Connecting ET 200SP
•
Supply voltages
•
PROFIBUS DP
•
Sensors and actuators
3
Configuring DP master (including PROFIBUS
address)
Documentation of the DP master
4
Inserting a SIMATIC memory card in the I-slave
(CPU)
SIMATIC memory card on the CPU
(Page 209)
5
Configuring I-slave (including PROFIBUS ad-
dress)
CPU 15xxSP-1 PN
http://support.automation.siemens
) and CM DP manual
6
Switching on supply voltages for DP master
Documentation of the DP master
7
Switching on supply voltages for I-slaves
CPU 15xxSP-1 PN
http://support.automation.siemens
) manual
8
Loading configuration in the DP master and I-
slaves
STEP 7 online help
9
Switching DP master and I-slaves to RUN
Documentation of the DP master
and CPU 15xxSP-1 PN
http://support.automation.siemens
) manual
10
Checking LEDs
CPU 15xxSP-1 PN
http://support.automation.siemens
) manual
11
Testing inputs and outputs
The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. See
the Test functions and fault resolu-
tion
http://support.automation.siemens
) section
Summary of Contents for Simantic ET200SP