Wiring
5.8 Connecting cable shields for I/O modules
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
93
Procedure
Watch the "Wiring BaseUnits" video sequence
http://support.automation.siemens.com/WW/view/en/95886218
To connect the cable shield, follow these steps:
1.
If necessary, connect the supply voltage L+ and ground to the BaseUnit.
2.
Press the shield contact up into the mount until you hear it click into place.
3.
Remove the cable insulation material around the shield terminal.
Connect the cable to the BaseUnit and place the cable in the shield contact.
4.
Insert the shield terminal into the shield contact.
5.
Tighten the shield terminal with approximately 0.5 Nm.
①
Mount
⑤
Insulation material removed (approx. 20
mm)
②
Supply voltage L+, ground
⑥
Cable to the encoder
③
Shield contact
⑦
Shield terminal
④
Flat connector for push-on contacts
(6.3 × 0.8 mm)
Figure 5-7
Mounting the shield contact