Maintenance
12.7 Resetting CPU/interface module (PROFINET) to factory settings
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
255
12.7.3
Resetting the interface module (PROFINET IO) to factory settings with a
RESET button
Requirement
The supply voltage to the interface module is turned on.
Required tools
3 to 3.5 mm screwdriver (for resetting with a RESET button)
Procedure
Proceed as follows to reset an interface module to factory settings by means of the RESET
button:
1.
Remove the interface module from the mounting rail (see Mounting the CPU/interface
module (Page 60)) and swivel it downwards.
2.
The RESET button is located on the rear of the interface module behind a small opening:
Press a screwdriver into the small opening for at least 3 seconds to activate the RESET
button.
3.
Install the interface module back on the mounting rail (see Mounting the CPU/interface
4.
Assign parameters to the interface module again.
①
Rear of the interface module
②
RESET button
Figure 12-6 RESET button
Summary of Contents for Simantic ET200SP