Commissioning
10.4 Startup of the ET 200SP with empty slots
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
209
Step
Procedure
See ...
8
Switching DP master to RUN
Documentation of the DP master
9
Checking LEDs
Interface module
http://support.automation.siemens
) Manual
10
Testing inputs and outputs
The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. Refer
to section Test functions and elimi-
nating problems (Page 259)
10.4
Startup of the ET 200SP with empty slots
Procedure
You can configure the ET 200SP distributed I/O system with any number of empty slots.
To build the ET 200SP distributed I/O system with any number of empty slots, follow these
steps:
1.
Cover all empty slots with BU covers.
2.
Finish the configuration with a server module.
Special consideration: A "Module missing in slot x" diagnostic message is generated by the
CPU/interface module for empty slots in which I/O modules are configured.
10.5
Removing/inserting a SIMATIC memory card on the CPU
Requirement
The CPU only supports pre-formatted SIMATIC memory cards. If necessary, delete all
previously stored data before using the SIMATIC memory card. Additional information about
deleting the contents of the SIMATIC memory card can be found in the section, SIMATIC
memory card - overview (Page 229).
In order to work with the SIMATIC memory card, first ensure that the SIMATIC memory card
is not write-protected. If it is, move the slider out of the lock position.