Distributed I/O system
32
System Manual, 12/2016, A5E03576849-AG
Application planning
3
Overview
The BaseUnits (BU) are classified according to different types. Every BaseUnit type is
distinguished by characteristics that match certain I/O modules and motor starters (see the
following table and graphics).
You recognize the BU type for an I/O module by the last two digits of an I/O module's article
number.
Note
You will find a complete overview of the possibilities of combining BaseUnits and I/O
modules /motor starters in the Product information for documentation of the ET 200SP I/O
system (
http://support.automation.siemens.com/WW/view/en/73021864
Table 3- 1
Selecting a suitable BaseUnit for I/O modules
Selecting a BaseUnit I/O module
(example)
Examples of suitable I/O modules for BU types
I/O module (example)
BaseUnit
BU type A0
See Digital, fail-safe,
Digital, fail-safe,
technology or com-
munication module
•
6ES7...A0
•
24 V DC
•
15 mm wide
DI 16×24VDC ST
(6ES7131-6BH00-0BA0)
BU15-P16+A0+2D
(6ES7193-6BP00-0DA0)
Analog module with-
out temperature
measurement**
•
6ES7...A1
•
24 V DC
•
15 mm wide
AI 4xU/I 2-wire ST
(6ES7134-6HD00-0BA1)
BU type A1
See Analog modules
(Page 37)
Analog module with
temperature meas-
urement*
•
6ES7...A1
•
24 V DC
•
15 mm wide
AI 4×RTD/TC 2-/3-/4-
wire HF
(6ES7134-6JD00-0CA1)
BU15-
P16+A0+2D/T(6ES7193-
6BP00-0DA1)