Configuring
6.1 Configuring ET 200SP
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
141
Requirements for configuration of the CPU
Table 6- 1
Requirement for installing the CPU
Configuration software
Requirements
Installation information
CPU 151xSP-1 PN:
STEP 7 (TIA Portal) as of
V13 Update 3
•
PROFINET IO
•
PROFIBUS DP (optional): With the communication
module CM DP
STEP 7 online help
CPU 151xSP F-1 PN:
STEP 7 (TIA Portal) as of
V13 SP1
CPU 151xSP-1PN (as of FW
version V1.8), CPU 151xSP
F-1 PN (as of FW version
V1.8):
STEP 7 (TIA Portal) as of
V13 SP1 Update 4
Requirements for configuration of the interface module
Table 6- 2
Requirement for installing the interface module
Configuration software
Requirements
Installation information
STEP 7 (TIA Portal) as of
V11 SP2*
•
PROFINET IO: As of Support Package HSP0024
STEP 7 online help
STEP 7 as of V5.5 SP2
•
PROFINET IO: GSD file GSDML-Vx.y-siemens-
et200sp-"Date in format yyyymmdd".xml
http://support.automation.siemens.com/WW/view/e
•
PROFIBUS DP: GSD file SI0xxxxx.gsx
http://support.automation.siemens.com/WW/view/e
Software of third-party manu-
facturer
Manufacturer documentation
* The TIA Portal supports GSDML specification V2.25. The ET 200SP distributed I/O system is delivered with a GSD file
based on specification V2.3. The GSD file can be installed in the TIA Portal and used without restrictions.
Configuring a motor starter
You configure SIMATIC ET 200SP motor starters in exactly the same way as the I/O
modules of the ET 200SP distributed I/O system.
The GSD files can be used with STEP 7
V5.5 SP4 and higher, and TIA Portal V13 SP1 and higher.