Configuration control (option handling)
9.3 Transferring control data record in the startup program of the CPU
Distributed I/O system
190
System Manual, 12/2016, A5E03576849-AG
Example in FBD: Use the LABEL (jump label) and JMP (jump at RLO=1) instructions
to program a loop.
Figure 9-5
WRREC
●
The control data record is stored retentively in the CPU. Note:
–
The retentivity of the control data record is independent of the retentivity settings in the
STEP 7 memory area. This means that the memory area in which the control data
record is configured does not have to be configured as retentive for this purpose.
–
If you write a control data record with modified configuration, the original data record
196 is deleted and the new data record 196 is saved retentively. The CPU will then
restart with the modified configuration.