Commissioning
10.2 Commissioning the ET 200SP for PROFINET IO
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
203
10.2.3
ET 200SP as an IO device
Configuration example
To use the ET 200SP distributed I/O system as an IO device, you need the IM 155-6 PNxx
interface module.
Figure 10-3 ET 200SP as an IO device
Commissioning procedure
For commissioning of the ET 200SP distributed I/O system as an IO device on the
PROFINET IO, we recommend the following procedure:
Table 10- 3 Procedure for commissioning the ET 200SP as an IO device for PROFINET IO
Step
Procedure
See ...
1
Installing ET 200SP
Section Installation (Page 54)
2
Connecting ET 200SP
•
Supply voltages
•
PROFINET IO
•
Sensors and actuators
4
Configuring IO controller
Documentation of the IO controller
5
Switching on supply voltages for the IO controller Documentation of the IO controller
6
Switching on supply voltages for IO devices
Interface module
http://support.automation.siemens
) Manual
7
Downloading the configuration to the IO controller STEP 7 online help
8
Switching IO controller to RUN mode
Documentation of the IO controller