Wiring
5.12 Connecting interfaces for communication
Distributed I/O system
120
System Manual, 12/2016, A5E03576849-AG
5.12.8
Connecting PROFINET IO to interface module via BA LC/FC BusAdapter
Introduction
You connect PROFINET IO to the interface module via the BA LC/FC BusAdapter:
●
Optically coupled to glass fiber-optic cables with an LC connector (port 1) or
●
Electrically with direct connection of the Fast Connect bus cable (port 2)
To do this, screw the BA LC/FC BusAdapter with the attached Fast Connect bus cable onto
the interface module and insert the LC connector.
You can loop through the PROFINET IO via the integrated 2-port switch. You can use any
port of the BusAdapter for feeding or for looping through. The integrated media converter
converts the signals automatically.
①
Glass fiber-optic cable LC
②
FastConnect FC
Figure 5-28 BA LC/FC BusAdapter
Attaching LC connectors
You can find more information about the required tools, accessories, requirements and
procedures in the section Connecting PROFINET IO to an interface module via BA 2×LC
BusAdapter (Page 115).
Connecting a Fast Connect bus cable
You can find more information about the required tools, accessories and procedures in the
section Connecting PROFINET IO to an interface module via BA 2×FC BusAdapter
(Page 104).