Wiring
5.12 Connecting interfaces for communication
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
115
5.12.6
Connecting PROFINET IO to the interface module via the BA 2xLC BusAdapter
Introduction
Via the BA 2xLC BusAdapter, you connect the PROFINET IO to the interface module
optically with fiber-optic cables using an LC connector. To do this, screw the BA 2xLC
BusAdapter onto the interface module and insert the LC connector. You can loop PROFINET
through optically via the integrated 2-port switch.
Figure 5-24 BA 2xLC BusAdapter
Required tools
3 to 3.5 mm screwdriver
Required accessories
●
If you prepare the FC FO cable with the IE FC FO LC plug, we recommend the FC FO
termination kit (LC) (6GK1900-0RL00-0AA0). You can cleave the glassfiber precisely
using the FC FO termination kit (LC).
CAUTION
Cleaving the glassfiber
•
Wear protective glasses during the cleaving process.
•
Dispose of the remaining fibers in a suitable waste container.
●
Connector for PROFINET connection: IE FC FO LC Plug (10 duplex plugs: 6GK1900-
1RB00-2AB0)
●
Fiber-optic cable:
–
IE FC FO Standard Cable GP (62.5/200/230) (6XV1847-2A)
–
IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C)
–
IE FC FO Robust Cable (6XV1873-5Rxx)
–
IE FC FO Standard Cable (6XV1873-3Axx)