Glossary
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
297
Fail-safe modules
ET 200SP modules with integrated safety functions that can be used for safety-related
operation (safety mode).
Fail-safe systems
Fail-safe systems (F-systems) remain in a safe state or immediately assume another safe
state as soon as particular failures occur.
Fault reaction time
The maximum fault reaction time of an F-system defines the interval between the occurrence
of any fault and a safe reaction at all affected fail-safe outputs.
For
→ F
-system overall:
The maximum fault reaction time defines the interval between the
occurrence of any fault in any → F
-I/O and a safe response at the relevant fail-safe output.
For digital inputs: The maximum fault reaction time defines the interval between the
occurrence of the fault and the safe reaction on the backplane bus.
For digital outputs: The maximum fault reaction time defines the interval between the
occurrence of the fault and the safe reaction at the digital output.
Fault tolerance time
The fault tolerance time of a process is the time a process can be left unattended without risk
to life and limb of the operating personnel, or damage to the environment.
Any type of F-system control is tolerated within this fault tolerance time, i.e. the
→ F
-system
can control its processes incorrectly or even not at all. The fault tolerance time depends on
the type of process and must be determined on a case-by-case basis.
F-CPU
An F-CPU is a central processing unit with fail-safe capability that is permitted for use in
SIMATIC Safety. A standard user program can also be run on the F-CPU.
F-I/O
Collective name for fail-safe inputs and outputs available in SIMATIC S7 for integration into
the SIMATIC Safety F-system. Available F-I/O modules:
●
Fail-safe I/O module for ET 200eco
●
Fail-safe signal modules S7-300 (F-SMs)
●
Fail-safe modules for ET 200S
●
Fail-safe modules for ET 200SP
●
Fail-safe DP standard slaves
●
Fail-safe PA field devices
●
Fail-safe IO devices