Wiring
5.12 Connecting interfaces for communication
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
107
BA 2×FC BusAdapter mounted
①
CPU
②
BA 2×FC BusAdapter
③
PROFINET connecting cable
④
Connection element
⑤
Interface module
Figure 5-17 Connecting the BA 2×FC BusAdapter to the CPU/interface module
Note
Installation guidelines for modules with PROFINET IO interfaces
Only when all connected nodes are equipped with a SELV/PELV power supply (or have
equivalent protection) is it permitted to operate the modules with PROFINET IO interfaces in
LANs (Local Area Networks).
A data transfer point is prescribed for connection to the WAN (Wide Area Network) that
guarantees this degree of safety.