Commissioning
10.3 Commissioning the ET 200SP on PROFIBUS DP
Distributed I/O system
204
System Manual, 12/2016, A5E03576849-AG
Step
Procedure
See ...
9
Checking LEDs
Interface module
http://support.automation.siemens
) Manual
10
Testing inputs and outputs
The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. Refer
to section Test functions and elimi-
10.3
Commissioning the ET 200SP on PROFIBUS DP
Requirements
●
The CPU/interface module is in the "Factory settings" status or has been reset to factory
settings (see section Interface module
http://support.automation.siemens.com/WW/view/en/55683316/133300
●
For CPU: The SIMATIC memory card is as delivered or has been formatted.
10.3.1
ET 200SP as a DP master
Configuration example
To use the ET 200SP distributed I/O system as a DP master, you need the CPU 151xSP-
1 PN and the CM DP communication module.
Figure 10-4 ET 200SP as a DP master