Configuration control (option handling)
9.2 Creating the control data record
Distributed I/O system
186
System Manual, 12/2016, A5E03576849-AG
Error messages
In case of error, the RDREC instruction returns the following error messages via the
STATUS block parameter while reading the feedback data record:
Table 9- 8
Error messages
Error code
Meaning
80B1
H
Invalid length; the length information in data record 197 is not
correct.
80B5
H
Configuration control not configured
80B8
H
Parameter error
The following events cause a parameter error:
•
Incorrect block ID in the header (not equal to 197)
•
Invalid version identifier in the header
•
A reserved bit has been set
•
The same slot in the station option has been assigned to more
than one slot in the station master
9.2.5
Data records and functions
Supported data records and functions
The table below shows a comparison of the supported data records and functions depending
on the CPU/interface module used.
CPU...
Interface module (IM...)
Supported data rec-
ords and functions
1510SP-1 PN
1510SP F-1 PN
1512SP-1 PN
1512SP F-1 PN
155-6 PN
HS
155-6 PN
HF
155-6 PN
ST
155-6 PN
BA
155-6 DP
HF
Control data record
(V2)
✓
✓
✓
✓
✓
✓
✓
Simplified control data
record (V1)
--
--
✓
✓
✓
✓
--
Read back control data
record *
✓
✓
✓
✓
✓
✓
✓
Read feedback data
record
--
--
✓
✓
✓
✓
✓
* You can read back the control data record with the RDREC instruction.