Maintenance
12.6 Firmware update
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
247
Options for the firmware update
The following options are available for updating firmware:
●
Online via PROFINET IO/PROFIBUS DP (with STEP 7)
●
Via a SIMATIC memory card (possible for CPU and centralized I/O modules)
●
Via the integrated Web server (possible for CPU as well as centralized and distributed I/O
modules)
Note
Firmware files of the CPU
If you perform a CPU update with STEP 7, you require STEP 7 (TIA Portal as of V13 Update
3).
The table below provides an overview of the media that can be used to update the firmware
of a specific module.
Table 12- 2 Overview of firmware update options
Firmware update
CPU
Interface module
I/O module
STEP 7 (TIA Portal)
✓
1)
✓
✓
STEP 7 (V5.5 SP2 or higher)
2)
--
✓
✓
SIMATIC Memory Card
✓
--
✓
Web server of the CPU
✓
--
✓
1)
V13 update 3 or higher
2)
If firmware files are only available in this format, you can also load the files via STEP 7
(TIA Portal), but not via a SIMATIC memory card and the Web server.
Firmware update for the motor starter
The following options are available for updating firmware for the motor starter.
●
Online via PROFINET IO/PROFIBUS DP (with STEP 7)
●
Via the integrated Web server (possible for CPU as well as centralized and distributed I/O
modules)
●
With the TIA Portal:
–
SIMATIC STEP 7 V13 SP1 or higher with installed HSP for the ET 200SP motor
starter
–
SIMATIC STEP 7 V14 or higher
Via a SIMATIC memory card
●
With SIMATIC STEP 7 Version V5.5 SP4 or higher
●
For fail-safe motor starters with the TIA Portal Version V14 SP1 or higher and installed
HSP.
Note
The firmware update for fail-safe motor starters must take place in a separate ET 200SP
system in which only the fail-safe motor starter to be updated is inserted.